The Maneuver popup provides control actions for the selected object, such as switching between operating modes or setting manual values. It only appears in the Tab menu when the object has signals matching one or more of the configured suffix aliases for the Maneuver popup.

Maneuver popup

This variant (ManoverBMS.kvie) is the layout used for building systems. It displays a Control section with the control actions available for the object. The layout depends on which suffix aliases are configured and which signals are present on the object. Typical elements include:

  • Mode buttons — buttons for switching between operating modes such as Auto, Off, and On. The currently active mode is indicated by a green status indicator above the corresponding button.
  • Status rows — read-only indicators showing the current state of a signal
  • Value rows — editable fields for entering manual values when a signal is configured as writable

Default suffix aliases

The following suffix aliases are configured for the BMS variant by default:

Suffix alias Suffix Writable Description
IO _IO Yes Off / On
manualControl _MAN Yes Manual control, digital output
manualControlAnalogOutput _MANA Yes Manual control, analog output
manualAnalogOutputValue _RMAN Yes Manual analog output signal
analogOutputValue _R No Analog output signal
commandOutput _M No Digital output signal
isOpen _IO No Open state
isClosed _IS No Closed state
isActive _IT No Active state
runningHours _DT No Running hours
runningHoursReset _DTA Yes Reset of running hours

Note