Maneuver¶
The Maneuver popup provides control actions for the selected object, such as switching between operating modes or setting manual values. It only appears in the Tab menu when the object has signals matching one or more of the configured suffix aliases for the Maneuver popup.
The popup comes in two variants, each with its own default suffix aliases: the Industry variant and the BMS variant. An object shows the variant whose suffix aliases match its signals.
Industry variant¶
The Industry variant (ManoverIndustry.kvie) is built for process equipment such as
pumps and motors. In addition to switching mode, it lets the operator give a manual
command and a manual setpoint, shows why an object cannot run, and can block an
object. The rows it shows are:
- Status — a card at the top showing the current state of the object.
- Operating mode — switches the object between Auto and Manual.
- Manual control — Off and On buttons for commanding the object by hand. They can only be used in Manual mode; until then the row reads "Select Manual to control".
- Manual setpoint — the setpoint the operator sets by hand. It is greyed out while the object is in Auto or blocked.
- Interlock — a text explaining why the object cannot run at the moment. It is shown in orange under Manual control, as "Interlock:" followed by the reason, and is absent when there is no interlock.
- Blocking — blocks the object so that it does not run, in either Auto or Manual. The row shows whether the object is blocked. To block it, enter a cause and press Block; a cause must be entered. While the object is blocked the row shows Blocked, the cause, the user who set the block and the time, and the button changes to Unblock. Unblocking returns the object to the mode it had.
- Status values — read-only values such as speed and power.
A control is enabled only when the user has the required privilege, the object is not blocked and, where a locking signal is configured, the object is in Manual.
The reason, the user and the time of each block are stored in the object_blocks
table in the Config database.
Default suffix aliases¶
The following suffix aliases are configured for the Industry variant by default:
| Suffix alias | Suffix | Writable | Description |
|---|---|---|---|
mode |
_MODE |
Yes | Operating mode (Auto / Manual) |
manualCommand |
_MANCMD |
Yes | Manual control |
manualSetpoint |
_MANSP |
Yes | Manual setpoint |
block |
_BLOCK |
Yes | Blocking |
interlock |
_ILKTXT |
No | Interlock text |
analogOutputValue |
_R |
No | Analog output signal |
isOpen |
_IO |
No | Open state |
RPM |
_RPM |
No | Speed |
Effekt |
_Effekt |
No | Power |
Note
The default suffix aliases can be modified and extended in Settings → Suffix → Suffix Alias - Popups. See Create Popup for more information.
BMS variant¶
This variant (ManoverBMS.kvie) is the layout used for building systems. It
displays a Control section with the control actions available for the object. The
layout depends on which suffix aliases are configured and which signals are present
on the object. Typical elements include:
- Mode buttons — buttons for switching between operating modes such as Auto, Off, and On. The currently active mode is indicated by a green status indicator above the corresponding button.
- Status rows — read-only indicators showing the current state of a signal
- Value rows — editable fields for entering manual values when a signal is configured as writable
Default suffix aliases¶
The following suffix aliases are configured for the BMS variant by default:
| Suffix alias | Suffix | Writable | Description |
|---|---|---|---|
IO |
_IO |
Yes | Off / On |
manualControl |
_MAN |
Yes | Manual control, digital output |
manualControlAnalogOutput |
_MANA |
Yes | Manual control, analog output |
manualAnalogOutputValue |
_RMAN |
Yes | Manual analog output signal |
analogOutputValue |
_R |
No | Analog output signal |
commandOutput |
_M |
No | Digital output signal |
isOpen |
_IO |
No | Open state |
isClosed |
_IS |
No | Closed state |
isActive |
_IT |
No | Active state |
runningHours |
_DT |
No | Running hours |
runningHoursReset |
_DTA |
Yes | Reset of running hours |
Note
The default suffix aliases can be modified and extended in Settings → Suffix → Suffix Alias - Popups. See Create Popup for more information.